40.5kV Kunze Vacuum Circuit Breaker
Chigadzirwa Overview Uye Kushandisa
ZW7A-40.5: CT yakavakirwa-mukati kana kunze, uye kunze kwekunze ndiko kutaridzika kwemuviri kwesilicone rubber kana porcelain.



Chigadzirwa Model Uye Zvinoreva

Mamiriro Ekushanda
Mamiriro ekushandisa akajairika
a.Ambient tembiricha yemhepo, shoma -30 °, yakakura +40 °;avhareji tembiricha kuyerwa mukati maawa makumi maviri nemana haapfuuri 35 °;
b.Kukwirira hakupfuuri 1000m;
c.Chiyero chekusvibiswa kwemhepo yakapoteredza haifaniri kudarika chikamu II;
d.Mhepo yakapoteredza haisi pachena yakasvibiswa neguruva, utsi, gasi rinopisa kana rinopisa, steam kana munyu spray;
e.Ukobvu hwe icing haifaniri kudarika 20mm;
f.Kumhanya kwemhepo hakusi kupfuura 34m/s;
g.Iyo seismic fissure haipfuuri madhigirii masere;
h.Humidity mamiriro:
Avhareji kukosha kwehunyoro hunyoro hwakayerwa mukati me24h, isingapfuuri 95%;
Avhareji kukosha kwehutsi hwemvura yakayerwa mukati me24h haipfuuri 2.2kPa;
Avhareji pamwedzi hunyoro hunyoro haupfuuri 90%;
Avhareji yemwedzi wega wega mhute yemvura haipfuure 1.8kPa;
Kana izvo zvataurwa pamusoro apa zvakajairwa kushandiswa zvakapfuura, ndapota bvunza mugadziri pachine nguva, uye ndapota tsanangura kana uchiodha;
Mamiriro ekushandisa asina kujairika
Kusanganisira iyo yakanyanya kushandiswa nharaunda senge kureba pamusoro pe1000 metres, kukurumidza kuchinja tembiricha, icing pamusoro pe20mm, kusvibiswa kwakanyanya, kunyungudika, ukuvhuvhu, jecha, guruva, kutonhora kwakanyanya, kupisa kunopisa, vibration, kukanganisa, swing, nezvimwe, ndapota taurirana advance kana muchihodha.
Main Technical Parameters YeZw7 Series Zvigadzirwa
Aihwa. | Tsanangudzo | Unit | Data | ||
1 | Rated voltage | kV | 40.5 | ||
2 | 1min Yakatemerwa simba frequency inomira voltage 1min | kV | 95 | ||
3 | Rated mheni impulse inomira voltage | kV | 185 | ||
4 | Rated frequency | Hz | 50 | ||
5 | Rated current | A | 630, 1250, 1600, 2000, 2500 | ||
6 | Yakatemerwa nguva pfupi inomira ikozvino | kA | 20 | 25 | 31.5 |
7 | Rated peak inomira ikozvino | 50 | 63 | 80 | |
8 | Rated short-circuit breaking current | 20 | 25 | 31.5 | |
9 | Rated short-circuit making current | 50 | 63 | 80 | |
10 | Yakatemerwa nguva pfupi-yedunhu | s | 4 | ||
11 | DC chikamu cheyakayerwa pfupi-yedunhu breaking ikozvino |
| 51 | ||
12 | Peak kukosha kweiyo transient recovery voltage (TRV) | kV | 114 | ||
13 | Yakatemerwa magetsi emagetsi ekuvhara nekuvhura zvishandiso uye anobatsira maseketi | V | DC/AC 220V, DC/AC 110V | ||
14 | Rated kushanda kutevedzana |
| O-0.3s-CO-15s-CO | ||
15 | Nguva yekuvhura | ms | 20~50 | ||
16 | Nguva yekuvhara | 30~80 | |||
17 | DC nguva yenguva yakayerwa pfupi-yedunhu breaking ikozvino | 45 | |||
18 | Rated tambo yekuchaja breaking current | A | 50 | ||
19 | Upenyu hwebasa |
| E2-C2-M2 (10000) | ||
20 | Rated short-circuit breaking current breaking times | Nguva | 20 |
Gungano Kugadzirisa Parameter Tafura YeZw7 Series Zvigadzirwa
Aihwa. | Tsanangudzo | Unit | Data |
1 | Bata kuvhura kureba | mm | 20±2 |
2 | Bata sitiroko | 4±1 | |
3 | Avhareji yekuvhara kumhanya (yero yekubata isati yavhara kusvika 10mm isati yavhara) | m/s | 0.8±0.3 |
4 | Avhareji yekuvhura kumhanya (yero yekubata inongopatsanurwa kusvika 10mm kure) | 1.6±0.3 | |
5 | Bounce nguva yekuvhara yekuvhara | ms | ≤5 |
6 | Bounce nguva yekuvhara yekuvhara | ≤2 | |
7 | Matatu-pole kusangana kuvhurwa munguva dzakasiyana | ≤2 | |
8 | Main circuit resistance yedanda rega rega | μΩ | ≤100 (Pasina chiridzwa chekushandura) |
9 | Ongorora: Aya ma paramita ari pamusoro anoreva iyo yakayerwa inoshanda voltage |
Installation Dimensions
Pakukwira kwemamita 1000 (pakati chinhambwe che710mm), kukwirira kwemamita 2000 (pakati kureba kwe780), uye urefu hwemamita 3000 (pakati chinhambwe che850), zviyero zvese zve circuit breaker ndezvizvi:

Pakukwira kwemamita 4000 (pakati chinhambwe 920), pa 5000 metres (center distance 1000) metres, zviyero zve circuit breaker ndezvizvi: